Single Phase and Three Phase Conventional ESP Power Supply.
Official Channel of Ador Powertron Limited in Russia
Single Phase and Three Phase Conventional ESP Power Supply.
Hermetically sealed construction
HV Transformer, Rectifier, AC Reactor & Choke Assembly is lid mounted for convenience and ease of maintenance and repairs.
Conforms to Ingress Protection class IP-65 as per IEC PUB 947-1. Doubly Wound, cross over winding with electrostatic shield between primary and secondary.
ADOR’s VERSATILE TR TANK CONSTRUCTION
– Sealed Corrugated Fin Tank (Hermetically Sealed Type).
– Hermetically Sealed Tank with Nitrogen Blanket.
– Tank with Radiator and Expansion conservator.
ALL TYPES OF MANUAL/MOTORISED/SOLENOID OPERATED H.T CHANGEOVER/GROUNDING SWITCHES/BUS COUPLERS
– Solenoid Operated Fail Safe H.T Grounding Switch.
– H.T Grounding Switch (Oil/Air).
– H.T Isolating Cum Grounding Switch.
– Bus-Couplers
BRIEF SPECIFICATION OF HV TR Set
Input Voltage |
380 V to 690 V |
Variation |
+/- 10% |
Frequency |
50 Hz / 60 Hz +/-5% |
Output Voltage |
30KV(P) to 200KV (P) On No Load at nominal rated I/P Voltage |
Output Current |
50mA to 4000mA Avg (mean) DC |
Design Form Factor |
1.2/ 1.3/ 1.4 MAX |
Design Ambient Temp |
-30 *C to +55 *C |
Humidity |
100% |
Various Configuration of Possible Ambient |
40/45/50/55 `C with top oil temperature rise limited to 55/50/45/40`C |
Bushing Orientation |
Horizontal/Vertical |
– Control Panel |
Natural Forced Air Cooled |
Oil Natural Air Natural |
|
– T/R Set |
Coolant: Miniral Oil/ Silicon Oil |